DIN Rail Mini Circuit Breaker

  • MCB (Earth Leakage) WSB9L-80
  • MCB (Earth Leakage) WSB9L-80
  • MCB (Earth Leakage) WSB9L-80
  • MCB (Earth Leakage) WSB9L-80
MCB (Earth Leakage) WSB9L-80 MCB (Earth Leakage) WSB9L-80 MCB (Earth Leakage) WSB9L-80 MCB (Earth Leakage) WSB9L-80

MCB (Earth Leakage) WSB9L-80

Key Information
WSB9L-80
Frequency: 50Hz/60Hz
Pole: 1P+N, 2P, 3P, 3P+N, 4P
Voltage: AC230V/400V
kA: 6kA(N); H:10kA(H)
Amps: 6, 10,16, 20, 25, 32, 40, 50, 63, 80
Width: 18, 36, 54, 72mm
Mounting: Din rail

Standard: IEC61009
General
WSB9L-80 series Earth Leakage Circuit Breaker (ELCB for short) is applies in circuit of AC 50/60Hz, rated voltage AC230, rated current upto 80A, for protection of electri shock and elelctricity leakage of equipments, overload and short circuit, also for infrequent changeover of lines under normal circumstance, are widely used at places of hotel, house, industrial & mining and similar buidlings.
The product meets standards of GB 16917.1 GB 16917.22.
Main technical parameters

Rated voltage (V)Initial stateRated residual action current IΔn (mA)Rated residual non-action current IΔno (mA)Max breaking timeRated short circuit breaking capacity (A)Type of instantaneous releaser
IΔn2IΔn5IΔn
AC2306, 10, 16, 20, 25, 32, 40, 50, 63, 8030150.20.10.046000C


Current rating (A)Test currentInitial stateTime limitExpected resultRemarks 
6, 10, 16, 20, 25, 32, 40, 50, 63, 801.13InCold t≤1h (6-63A)Not tripping
t≤2h (80A)Tripping 
1.45InThermal t<1h (6-63A)Tripping Current rise to the set value in 5s steadily
t<2h (80A)Tripping 
2.55InCold 1sTripping In≤32A
1sIn>32A
C5InCold t≤0.1sNot trippingConnect the current by closed auxiliary switch
10Int<0.1sTripping 


Contact Us

Contact: westhomes

Phone: 0097142210039/0097142297823

Tel: 05666-16680

E-mail: westhomeshhz@gmail.com

Add: Show Room No.1-Sabkha UAE SHOWROOM